VM600 IOC4T input/output card

Date: Dec 31, 2024Views:

  The IOC4T input /output card acts as a signal interface for the VM600 series MPC4 machinery protection card, from Meggitt’s Vibro-Meter® product line. It is installed in the rear of a VM600 rack and connects directly to the rack backplane via two connectors. Each IOC4T card is associated with a corresponding MPC4 card and is mounted directly behind it in the VM600 rack (ABE04x or ABE056). The IOC4T operates in slave mode and communicates with the MPC4, through connector P2, using an Industry Pack (IP) interface.

  The front panel of the IOC4T (rear of the VM600 rack) contains terminal strip connectors for wiring to the transmission cables coming from measurement chains (sensors and /or signal conditioners). The screw-terminal connectors are also used to input all signals from and output all signals to any external control system.

  The IOC4T card protects all inputs and outputs against electromagnetic interference (EMI) and signal surges and also meets electromagnetic compatibility (EMC) standards.

  The IOC4T connects the raw dynamic (vibration) and speed signals from the sensors to the MPC4. These signals, once processed, are passed back to the IOC4T and made available on the terminal strip on its front panel (rear of VM600). For the dynamic signals, four on-board digital-to-analog converters (DACs) provide calibrated signal outputs in the range 0 to 10 V. In addition, four on-board voltage-to-current converters allow the signals to be provided as current outputs in the range 4 to 20 mA (jumper selectable).

  The IOC4T contains four local relays that can be attributed to any specific alarm signals under software control. For example, these may be used to signal an MPC4 fault or a problem detected by a common alarm (Sensor OK, Alarm and Danger) in a typical application.

  In addition, 32 digital signals representing alarms are passed to the rack backplane and may be used by optional RLC16 relay cards and / or IRC4 intelligent relay cards mounted in the rack (jumper selectable).

  Applications information

  When used as a card pair with an MPC4 machinery protection card, the IOC4T is highly suitable for machinery monitoring and protection in a wide range of industrial applications.

  For further information on the use of MPC4/IOC4T card pairs in general, refer to the VM600 machinery protection system (MPS) hardware manual and the VM600 MPSx software manuals. For information on the use of MPC4/IOC4T card pairs in functional safety contexts, refer to the refer to the VM600 functional safety manual.

  For specific applications, contact your local Meggitt representative.

  Dynamic signal inputs

  Filtered for protection against electromagnetic interference (conforms to EC standards). Refer to the VM600 MPC4 machinery protection card data sheet for further information.

  Buffered dynamic signal outputs

  Filtered for protection against electromagnetic interference (conforms to EC standards). Refer to the VM600 MPC4 machinery protection card data sheet for further information.

  Speed/phase reference inputs

  Filtered for protection against electromagnetic interference (conforms to EC standards). Refer to the VM600 MPC4 machinery protection card data sheet for further information.

  Discrete signal interface (DSI) inputs

  A closed contact between the DSI AR and DSI RET inputs resets (clears) the alarms latched by the MPC4/IOC4T card pair. Note: The alarm reset input (DSI AR) is edge-sensitive and a high-tolow transition is required to activate the reset.

  A closed contact between the DSI DB and DSI RET inputs inhibits (bypasses) the danger relay outputs

  A closed contact between the DSI TM and DSI RET inputs multiplies the alarm levels by a scale factor (software configurable), to enable adaptive monitoring.

  Detection of an open circuit or a closed circuit on the input

  Alarm outputs

  The MPC4 card can drive the four local relays on the IOC4T card, as well the relays on RLC16 relay cards and/or IRC4 intelligent relay cards using the VM600 rack’s Raw bus or Open Collector (OC) bus. For IOC4T card relay features, see Relay characteristics on page 4. For further information on RLC16 or IRC4 relay cards, refer to the corresponding data sheet.

  Analog (DC) outputs

  Current output (4 to 20 mA) or voltage output (0 to 10 V), individually selectable by a jumper on the IOC4T for each output. Note: For current outputs, the analog output is actually driven in a slightly wider 2 to 23 mA range, proportional to the input signal.

VM600 IOC4T.pdf


Related product recommendations:

VM600-CSA
VM600-ABE042
VM600 RPS6U
VM600 RPS6U 200-582-200-011
VM600 RLC16 200-570-000-111
VM600 RLC16
VM600 MPC4 200-510-017-019
VM600 MPC4 200-510-017-019 200-510-111-013
VM600 MPC4 200-510-111-013
VM600 MPC4
VM600 RLC16 200-570-101-015
VM600 RPS6U 200-582-600-013
VM600-ABE042 204-042-100-011
VM600-CSA 204-040-100-211
More......

RELATED ARTICLE

Shanxi Runsheng Import and Export Co., Ltd

Address: 3301, Building A, Wanda Center, No. 175 Jiefang Road, Xinghualing District, Taiyuan City, Shanxi Province
Google email: wkcarshop666888@gmail.com
Industrial Control Sales Consultant: Amelia
Whatsapp: +86 18030295882

Copyright © 2023~2024 Shanxi Runsheng Import and Export Co., Ltd