Multilin F650 Cost effective protection, automation and control of distribution feeders

Date: Sept 24, 2024Views:


  The Multilin™ F650 has been designed for the protection, control and automation of feeders or relatedapplications. The Multilin F650 provides high speed protection and control for feeder management andbay control applications, and comes with a large LCD and single line diagrams that can be built for bay monitoring and control for various feeder arrangements including ring-bus, double breaker or for breaker and half.

  Designed with advanced communications options and detailed monitoring capabilities, the Multilin F650 provides advanced functionality, including high-performance protection, extensive control functions and flexible configuration capabilities. The Multilin F650 can also be used for a variety of applications other than feeder protection and control.


  Key Benefits

  • Comprehensive and flexible protection and control device for feeder applications

  • Increased system uptime and improved system stability with load shedding and transfer schemes

  • Advanced automation capabilities for customized protection and control solutions

  • Human Machine Interface (HMI) with graphical LCD, programmable buttons, and easy keys for selecting setting menus, and submenus

  • Reduced replacement time with modular draw-out construction

  • Reduced troubleshooting time and maintenance costs with IEEE® 1588 (PTP), IRIG-B and SNTP time synchronization (configuration of two different SNTP masters), event reports, waveform capture, and data logger

  • Simplified system integration with communications supporting serial and Ethernet interfaces as well as multiple protocols

  • Embedded IEC® 61850 protocol (and support for edition 2), IEC 60870-5-103/104, IEC 62439/PRP/HSR,IEEE 802.1D/RSTP

  • Proven interoperability and KEMA 61850 Edition 2 certified


  Applications

  • Primary or back-up protection and control for feeders on solidly grounded, high impedance grounded or resonant (Peterson Coil) grounded systems

  • Bus blocking/interlocking schemes

  • High-speed fault detection for arc flash

  • Throw over schemes (bus transfer scheme applications)

  • Load shedding schemes based on voltage and frequency elements

  • Distributed Generation (DG) interconnect protection, including active and passive anti-islanding


  Protection & Control

  • Time, instantaneous & directional phase, neutral,ground and sensitive ground overcurrent

  • 2nd Harmonic restraint

  • CT Supervision

  • Manual close with cold load pick up control,forward power and directional power units

  • Load encroachment supervision

  • Wattmetric ground fault detection

  • Positive and negative sequence based over/under voltage elements

  • Four-shot autorecloser with synchronism check

  • Trip circuit supervision, breaker control and breaker failure

  • Frequency protection (rate of change and six stages of under and over frequency)

  • Broken conductor and locked rotor

  • Programmable digital inputs and outputs

  • 6 Setting Groups


  Monitoring & Metering

  • Fault locator, fault and event recorder

  • Comprehensive breaker monitoring

  • High resolution oscillography and data logger with programmable sampling rate

  • Metering: V, I, Hz, W, VA, PF

  • Demand: Ia, Ib, Ic, Ig, Isg, I2, MW, MVA


  EnerVista Software

  • Simplified setup, configuration and commissioning

  • Strong document archive and management system

  • Simplified full featured monitoring and data recording

  • Seamless integration toolkit


  Protection and Control

  The F650 provides high speed protection and control for feeder management and bay control applications, including:

  Overcurrent Protection

  Instantaneous and time overcurrent functions are available for phase, neutral, ground/sensitive ground and negative sequence currents. A variety of time curves are provided including

  IEEE/ANSI®, IEC A/B/C/long time inverse/short time inverse, GE IAC, I2t, definite time, rectifier curve and four user-programmable curves.

  Directional supervision is available for phase, neutral, ground and sensitive ground currents.


  The neutral/ground directional elements

  can be programmed to work under zerosequence voltage, ground sensitive current or dual polarization.

  Over/Under Voltage Protection

  The F650 includes the following voltage elements:

  • Phase undervoltage/overvoltage elements (each element has three individual phase undervoltage/overvoltage components)

  • Auxiliary undervoltage/overvoltageelement

  • Neutral overvoltage element

  Following are some of the key applications where voltage elements can be used:

  • Source transfer schemes

  • Load shedding schemes

  • Back up capacitor bank protection and control

  • Backup motor protection to prevent automatic restart

  Over/Under Frequency Protection

  The F650 offer six stages of overfrequency and underfrequency elements to improve network (grid) stability using voltage or frequency based loadshedding techniques. It also allows to

  provide back up protection and trip breakers directly when protecting feeders and other frequency sensitive power equipment.

  Frequency Rate of Change Protection

  Frequency rate of change (df/dt) elements included in the F650 provide protection against system disturbances through load shedding.

  Wattmetric Zero-sequence Directional

  Applications include ground fault protection in solidly grounded transmission networks, grounded/ungrounded/resistor-grounded/resonant-grounded distribution networks. The wattmetric zero-sequence directional element responds to power derived from zero-sequence voltage and current in a direction specified by the element characteristic angle. The angle

  can be set within all four quadrants and the power can be active or reactive. Therefore, the element may be used to sense either forward or reverse ground faults in either inductive,

  capacitive or resistive networks. The inverse time characteristic allows time coordination of elements across the network.

f650_gea-12818b.pdf


Related product recommendations:
IS200AEPAH1BKE
IS215WEPAH2B
IS420YAICS1B
IS200SPIDG1ABA
IS200SDIIH1ADB
IS200SPROH1AAB
IS200SRTDH2ACB
IS200STCIH2A
IS200STCIH2A-DD
IS200STCIH6AED
IS200TBCIH2CAA
IS200TBCIH1BBC
IS200TBCIH2CAA
IS200TDBTH6ACD
IS200TDBTH6ABC
IS200TPROH1BCB
IS200TPROS1CBB
IS230TSPRH1C
IS200TPROS1CBB
IS230TNEAH2A
IS200TREAH2AED
IS200ECTBG1ADE
IS215WETAH1BB
IS200TSVCH2ADC
F650BFCF1G0HI6E
F650-FEEDERFMOD36-04/BAY
F650BFBF2G1HI6H
F650BABF1G1HIE
F650BFBF2G1HI6
F650BFBF1G0HICE
F650BABF2G1HI
F650BABF1G0HIC
F650BFBF1G0HI
F650BFCF2G0HI
more......

RELATED ARTICLE

Shanxi Runsheng Import and Export Co., Ltd

Address: 3301, Building A, Wanda Center, No. 175 Jiefang Road, Xinghualing District, Taiyuan City, Shanxi Province
Google email: wkcarshop666888@gmail.com
Industrial Control Sales Consultant: Amelia
Whatsapp: +86 18030295882

Copyright © 2023~2024 Shanxi Runsheng Import and Export Co., Ltd