RS-FS-9009-03 | UV Flame Sensor | Reuter-Stokes | GE | RS-FS-9009-03

Using silicon carbide (SiC) photodiode technology, it has high sensitivity to ultraviolet wavelengths (especially long-wave UV) and can penetrate fuel/steam mist. The sensitivity is 10 times that of traditional tubular sensors, and the response time is ≤25 milliseconds. It supports rapid flame status feedback to ensure uninterrupted service. It is widely used in key fields such as gas turbines, petrochemicals, and power, and is a core equipment for ensuring industrial combustion safety and efficiency.

PRODUCT TAGS

  Many products are not yet available. Please contact us for more information.

  If the product model number differs from the displayed image, the model number will prevail. Please contact us for specific product images, and we will arrange to take photos at the warehouse for verification.

  We have 76 shared warehouses worldwide, so it may sometimes take several hours for us to accurately respond to your request. We apologize for this. Of course, we will respond to your inquiries as soon as possible.


  RS-FS-9009-03 Other Names:

  Flame Tracker Sensor RS-FS-9009-03

  RS-FS-9009-03 Flame Tracker

  Flame Detector RS-FS-9009-03

  Core Technology: Utilizing a silicon carbide (SiC) photodiode, this sensor is highly sensitive to long-wave UV light (UV-C to UV-B) and can penetrate fuel vapor mist, achieving a fast response (<25 milliseconds) and a wide dynamic range. Compared to traditional short-wave UV sensors, it offers enhanced interference resistance and is suitable for low-NOx burners and steam injection applications.

  Response Time: ≤25 milliseconds, enabling rapid flame status feedback and ensuring uninterrupted service.

  Output Signal: 4-20mA industrial standard analog signal, compatible with various control systems; supports both digital and analog outputs.


  Key Technical Specifications

  Electrical Parameters: Operating voltage: 24V DC (12-30V), output: 4-20mA analog signal, power consumption: approximately 100mA, supports industry-standard interfaces (such as RS-422).

  Environmental Adaptability: Operating temperature: -30°C to 150°C (water/air cooling required for high-temperature scenarios), pressure resistance: 400psi, protection level meets ATEX/IECEx and other explosion-proof certifications, suitable for hazardous areas.

  Mechanical Design: 316 stainless steel housing, MIL-C-38999 military-spec connector, quick disconnect design (reducing replacement time from hours to minutes), resistant to vibration and contaminants (such as fouling detection).

  Anti-interference Design: Shields against false alarm sources such as welding arc light, sunlight, and headlights, and features built-in optical channel contamination monitoring and window fouling detection.

  Application Scenarios and Advantages

  Core Applications: Gas turbine combustor monitoring, boiler/petrochemical unit flame verification, steel blast furnace heat treatment, and power facility safety protection. Supports multi-fuel (natural gas, oil, etc.) and low-NOx burners, and is compatible with steam injection scenarios.


  Performance Advantages:

  High Sensitivity and Fast Response: Detects flame status within 25 milliseconds, reducing downtime risk.

  Low Maintenance: Optimized cooling system extends electronics life, and quick-change design reduces maintenance costs.

  Anti-Interference Capability: The algorithm suppresses false alarms from welding arcs, sunlight, and lighting, meeting NFPA gas turbine flame detection standards.

  Low-Voltage Operation: Eliminates the need for high-voltage wiring, simplifying installation and reducing the need for explosion-proof conduits.


  Industrial Applications:

  Power: Gas turbines, boilers, and power plant combustion control systems.

  Petrochemical: Refineries, petrochemical reactors, and heating furnaces.

  Metallurgy: Blast furnaces, converters, and industrial kilns.

  Other: Marine propulsion, natural gas pipelines, and industrial burners.

  Special Advantages: Supports water-wash process operation, is compatible with multiple fuels (gas and oil), and is suitable for low-NOx combustion and steam injection conditions.


  Installation and Maintenance Key Points

  Installation Specifications: Grounding and lightning protection are required (multiple grounding points on the coaxial cable metal sheath, with a lightning arrester grounding resistance ≤ 5Ω). Avoid intertwining signal and power cables to prevent lightning-induced interference.

  Maintenance and Upgrades: Customized conversion kits are available, compatible with the mechanical/electrical interfaces of older systems, supporting continuous operation during water-wash processes and extending equipment life.

  Self-Diagnostics: Monitors optical channel contamination and window fouling, and reports abnormalities to the control system through system self-diagnosis.


  Certifications and Compliance

  Safety Certifications: ETL, ATEX, and IECEx certified, suitable for use in explosion-hazardous areas, and complies with NFPA gas turbine flame detection specifications.

  Designed for Reliability: AISI 316/304 stainless steel housing, argon-filled and sealed, provides vibration and shock resistance, meeting the requirements of harsh industrial environments.

  Low-Voltage Operation: Eliminates the need for high-voltage wiring, reduces the need for explosion-proof conduits, and reduces installation complexity.


  Summary

  The RS-FS-9009-03 is a high-performance sensor designed by Reuter-Stokes (now part of GE) specifically for industrial flame detection. With its high sensitivity, fast response, anti-interference capabilities, and low maintenance, it is widely used in critical applications such as gas turbines, petrochemicals, and power generation, serving as a core device for ensuring industrial combustion safety and efficiency.


  All products on this website are specialty products, and market prices fluctuate.

  Please refer to customer service for specific quotes. Since these products are new, prices are not guaranteed.

  Please confirm model, product, price, and other details with customer service before placing an order. This website is used.

  New products are currently for sale. Please contact customer service for details.


Related product recommendations:
GC868-2-21-10416-0-0

GF868-2-11-20814-11-0-0-0
GF868-1-2-1-2-1-B-1-4-0-0-0-CC-RPT
GF868-1-2 GE
GF868-1-31-21A14-FM-0-0
GF868-1-11-10114 GE
GE MVR1600-4601
GE MVR1600-4601-A
IS420YDOAS1B
IS420PUAAH1A
IS420ESWBH3A-C
IS420YAICS1B
IS420ESWBESWB
IS420UCSCH2A-E-V0.1-A
IS420UCSBH3A
IS420UCSBS1A
IS420ESWAH1A
IS420PPNGH1A
IS420ESWBH3A-ESWA
IS420UCECH1B-A
More.....

PRODUCT TAGS

Shanxi Runsheng Import and Export Co., Ltd

Address: 3301, Building A, Wanda Center, No. 175 Jiefang Road, Xinghualing District, Taiyuan City, Shanxi Province
Google email: wkcarshop666888@gmail.com
Industrial Control Sales Consultant: Amelia
Whatsapp: +86 18030295882

Copyright © 2023~2024 Shanxi Runsheng Import and Export Co., Ltd