GE WESTERM D20 M D20 D200 Substation Controllers
D20 Chassis (single-slot, non-VME)
The D20 chassis is a 3U horizontal slot chassis. The non-VME version of
the D20 chassis is equipped with a rear-mounted termination board that
provides power connection and serial port access to the D20 system.
Non-VME versions of the D20 provide a single horizontal Eurocard slot, into
which the D20ME board is installed.
Many products have not been listed yet. For more products, please contact us
If the product model is inconsistent with the displayed image, the model shall prevail. Please contact us for specific product images, and we will arrange for photos to be taken and confirmed in the warehouse
We have 16 shared warehouses worldwide, so sometimes it may take several hours to accurately return to you. We apologize for any inconvenience caused. Of course, we will respond to your concerns as soon as possible.
MultilinD20/D200 Substation 
Controllers Simple to Advanced Substation Automation Control The Multilin 
D20/D200 Substation Controllers offer an industry leading design embedded with 
high value substation automation applications that provide cost savings, 
increased reliability, and improved operational efficiencies in electric power 
substations. The ability to support a wide range of communication protocols and 
applications,

  allows 
the D20 to be interoperable with a broad range of intelligent electronic slave 
and master devices. The D20 can execute simple to complex local logic, compile 
and process data [collect and convert] and reports upstream to master stations. 
The D20’s distributed, expandable I/O architecture 
and mission-critical automation control applications reinforce why the D20 
controller is being used in over 40,000 installations around the world. Key 
Benefits In a mission-critical substation-hardened package, the D20/D200 
provides:https://www.axcontroler.com/
 •Substation client and server functionalities by maintaining a 
distributed architecture for gathering and controlling data on substation 
equipment while sending data to master stations via serial RS-232, RS-485, fibre 
optic or Ethernet interfaces for point to point, multi-drop and remote 
connections.
•Support for a broad range of SCADA host protocols, IED 
protocols, Communication options, Input/output (I/O) peripheral modules, and 
operation and maintenance utilities substation automation applications. Refer to 
the hardware manual and see the appendix section of this document for more 
details. Applications Functionalities such as data concentrator, protocol 
converter or a local automation platform to implement popular distribution 
automation applications such as capacitor bank control, outage prevention 
programs, feeder resource optimization and control interlocking inhibition and 
subgrouping. Functionalities such as data concentrator, protocol converter or a 
local automation platform to implement popular distribution automation 
applications such as capacitor bank control, outage prevention programs, feeder 
resource optimization and control interlocking inhibition and subgrouping.

•Data Concentrator Automatically consolidates collected information from 
intelligent electrical devices (IEDs), such as relays and meters, and 
communicates to SCADA, EMS, DMS and Data Historian systems
•Protocol 
Converter Translates different data message formats between devices to support 
interoperability
•Local Automation Platform Implements popular distribution 
automation applications such as capacitor bank control, outage prevention 
programs, feeder resource optimization and control interlocking, inhibition and 
subgrouping
  Substation Controller Connectivity 
The D20/D200 can support a wide range of substation automation communication 
protocols and enhanced SCADA applications. See Appendix B for a list of 
supported protocols for both client and server devices. The following summarizes 
some of the different data translation applications that are equipped in the 
D20/D200. Multilin D20/D200 Data Translation Applications User Programmable 
Logic:
•LogicLinxmodule: IEC61131-3 compliant PLC-type logic with full 
support for 5 programming languages
•Calculator module: Soft logic utility 
to perform mathematical and logical operations Generation, Transmission, and 
Feeder Bay Automation Applications: • 
Automatic Voltage Control module: Maintains steady voltage base on user-defined 
targets and settings •Local / Remote Data Translation module: A master 
local/remote switch to control the local/remote state of distributed 
devices
•Secondary Master Trip/Close module: Enables the use of individual 
relays (with external terminations) as master trip/close relays
•Set-point 
Adjustment module: Adjust set points based on control request durations or 
analog input values
•Tap Position Indication module: Translates status 
points into scaled analog input values to reflect transformer tap 
positions Distribution 
Automation Applications:
•Auto Reclose: Automatically 
reclose tripped circuit breakers following momentary faults • Automatic 
Restoration: Patented load transfer scheme isolates faults and restores power to 
non-faulted sections if possible

•Distribution Capacitor Control 
Algorithm: Improves reactive support during peak 
periods through more effective use of existing capacitor banks
•Fault 
Localization: Locates and isolate faults to reduce 
customer outage times
•Load and 
Dead Bus Transfer: Monitors a network of 
substations and move load off overloaded transformers to other stations as 
required
•Load 
Shedding/Curtailment: Sheds load intelligently 
during overload conditions Data Logging / Storage Applications:
•SOE Local 
Logger: Logs digital and analog SOEs to an external 
printer, PC or to a CSV file
•Accumulator Freeze: Coordinates freezing of 
accumulator groups
•Event 
Storage: Stores history of current values, status, 
and time-tags of analogs and accumulators for up to 7 days
•Historical 
Analog: Stores averaged historical values for up to 
8 analog inputs Communication Services Applications:
•Communication 
Watchdog: Monitors and report the health of 
communications
•Substation 
Maintenance: Suppresses SCADA point reporting 
during substation maintenance
•Virtual Terminal: Directs remote access to 
connected devices
•Line 
Switch: Monitors main and secondary communication 
channels and retransmits on a third channel
•LAN 
Services: TFTP, SPT Server/Client, Time 
Server/Client
•COM 
Statistics: Records a detailed communication 
pass/fail statistics
•IRIG B 
Source: Time sync connected devices using 
IRIG-B
•SNTP 
Client: Time sync over an Ethernet LAN Data 
Reduction and Summarizing Applications:
•Analog 
Reference: Monitors analog input hardware for good 
or bad reference values
•Data 
Change Detect: Toggles a status point every time 
any data in a configured group changes
•Alarm 
Prioritization: An alarm filter designed to manage 
the 3 level alarms reported by GE’s DART pole-top/pad-mount distribution 
RTU
•Analog 
Averaging: Averages analogs at regular 
intervals
•General 
Alarm: Groups alarms together to create summary 
alarms
•Top of Hour (TOH) Analog 
Averaging: Averages analogs at regular intervals 
relative to the top of the hour • Redundant I/O: Provides data from a backup 
source if the primary source is off-line Data Conversion Applications:
•Digital-Analog Value 
Conversion: Converts digital input groups to analog 
data using binary, BCD, or gray code encoding
•Digital Input to 
Counter: Counts the number of SOE or COS 
transitions on status points
•BCD 
Setpoint: Translates analog output requests into a 
group of BCD encoded control points • Accumulator Delta to Analog: Converts 
accumulators to analog values for protocols that do not support 
counters
•Time 
Stamp: Interprets each bit in an analog input as a 
status point, and create SOEs appropriately
•Analog to Digital 
Conversion: Converts analog inputs into groups of 
binary coded control outputs
•Mailbox: Converts analog outputs 
into analog inputs so they can be read by all 
masters https://www.axcontroler.com/
Configuration 
and Maintenance Facility The D20/D200 is equipped with a range of maintenance 
utilities to assist the user in configuring, testing and monitoring the system. 
ConfigPro ConfigPro is a tool, installed on a personal computer, which helps you 
manage information associated with your GE Energy equipment. The primary use of 
ConfigPro is to facilitate the configuration of D20/D200 hardware and software 
through the maintenance port on the main processor and I/O peripheral. 
Information is accessed through a hierarchy of windows, as 
follows:
Project Window: Provides a graphical 
representation of your project. Each device in the project is represented by a 
corresponding icon. Connections between devices are shown by a series of lines 
and arrows.
Device Window: When you 
double-click on a device, the device window is opened in the main area. The 
device window will display all of the configurable applications for the 
device.
The device window has four 
tabs:
•Data collection applications
•Data 
translation applications
•System point database 
applications
•Data 
processing applications Application 
Window: Displays the tables for a particular 
application Report Window: Allows you to select and print reports. SGConfig 
SGConfig is the latest software used to configure D20/D200. SGConfig 
replaces ConfigPro because it supports Windows 7 - 32 and 64-bit operating 
systems while maintaining backwards compatibility with Windows XP. It is a PC 
software-based user interface that allows users of GE Substation Gateways to 
efficiently manage configuration files for the RTUs series of Substation 
controllers. SGConfig includes all of the functionality available in the 
ConfigPro software, provides enhanced visual representation of your substation 
hardware configuration and device software configuration. In addition to the 
ConfigPro functionality, SGConfig provides support for::
•Importing 
and exporting xml representation of D2x devices
•D25 KT control card
•D25 Ethernet 100/10 MB card
•Secure configuration transfer to/from D20 
devices with D20MX processors over Ethernet connections.
D200 Chassis (multiple-slot, VME]
The D200 chassis is equipped with a rear-mounted termination board for
power connections and serial-port access.
The D200 has the computing power and expandability needed to provide
substation automation in larger substations. This is achieved through an
innovative design that employs multiple D20 processors, communicating
over a VME bus:
• RS-232/RS-485 ports support large numbers of host systems and IEDs
• VME bus architecture provides high scalability and performance for
adding serial ports, LAN options, and memory
• Data is integrated and coordinated, so different applications access a
single, real-time database
• Optional redundant configuration for high reliability at critical sites
• ironment, in accordance with applicable IEEE® and IEC® standards
D200 hardware is similar in design to the D20 hardware, but it has
significantly more physical capacity. Based on a 9-slot VME chassis, the
D200 illustrated in figure 4 can support up to:
• 4 D.20 ports, each supporting up to 31 I/O peripherals, without repeaters,
and 120 I/O peripherals, with repeaters
• 49 RS-232 or RS-485 ports (seven per D20ME or D20ME II Main Processor)
• Two Ethernet channels